APSAD R7 maintenance: the annual checklist that secures your insurance
Updated :
Updated :
Most fire insurance contracts contain an APSAD R7 clause that operators often overlook. Here's the annual checklist to stay covered and audit your provider.
APSAD R7 (CNPP) defines the service requirements applicable to fire detection system (SDI) maintenance. It certifies both the provider's competence (Q7) and the intervention quality (R7) via independent annual audits.
Every visit must produce a signed, timestamped report kept for at least 5 years. Serious providers expose a digital platform with insurer access.
Kept up to date by the operator, it logs EVERY intervention (maintenance, tests, faults, alarms). Enforceable document in case of incident.
The contract must guarantee exclusive use of EN54-certified parts from the original manufacturer. Generic components void the installer's warranty.
Annual evacuation training is mandatory (French Labour Code R4227-39), including a fire drill with archived attendance log.
Yes, and it happens regularly. The APSAD R7 clause is a contractual condition: any documented breach lets the insurer invoke an exclusion. Keep 5 years of timestamped reports.
Ask for the CNPP certification number (Qn° / Rn° format) and verify it on cnpp.com. Certifications are annual: a provider whose certification has lapsed no longer covers your installations.
Between 4% and 7% of the initial SDI value, depending on site complexity. Roughly €3,000 ex-VAT/year for a small ERP, up to €35,000 ex-VAT/year for a multi-building Seveso site.
Schedule a catch-up visit within 30 days with a specific report stating the delay and its cause. Beyond 30 days, run a full ad-hoc inspection and notify the insurer.