Most fire insurance contracts contain an APSAD R7 clause that operators often overlook. Here's the annual checklist to stay covered and audit your provider.

What does APSAD R7 actually cover?

APSAD R7 (CNPP) defines the service requirements applicable to fire detection system (SDI) maintenance. It certifies both the provider's competence (Q7) and the intervention quality (R7) via independent annual audits.

What are the 5 critical points to verify?

1. Visit frequency

  • 4 quarterly visits: sounder tests, batteries, alarm relay check
  • 1 in-depth annual visit: per-detector smoke test, chamber sensitivity, panel calibration
  • 1 ad-hoc visit after any incident or installation change

2. Timestamped digital reports

Every visit must produce a signed, timestamped report kept for at least 5 years. Serious providers expose a digital platform with insurer access.

3. Fire safety register

Kept up to date by the operator, it logs EVERY intervention (maintenance, tests, faults, alarms). Enforceable document in case of incident.

4. Certified spare parts

The contract must guarantee exclusive use of EN54-certified parts from the original manufacturer. Generic components void the installer's warranty.

5. Continuous staff training

Annual evacuation training is mandatory (French Labour Code R4227-39), including a fire drill with archived attendance log.